-
1,09 zł netto
ETP4890-A2 is an efficient telecommunications power station equipped with three R4830G rectifiers with a current of 30A. The total output current of the entire device is 90A, at 53.5V DC it gives a total of about 4800 W of power. The output voltage range is -42 ~ -58V DC (default value is -53.5V), and input voltage 85 - 300V AC (at 45 ~ 66 Hz). The maximum number of power lines is 4.
The set includes an SMU01C controller equipped with a DB 50 connector. In addition, it has an RS232/485 console port and an LCD display. It supports Huawei protocol "access network point-to-point" so it can be connected to U2000. On the front of the controller, in addition to the display, there are buttons to control, two LEDs (one informing about work, the other informing about alarm), and the entrance to the temperature sensor.
The most important features:
- SMU01C controller;
- 3 R4830G rectifiers;
- total output current 90 A;
- total output power 4800 W for -53,5 V DC;
- input voltage range: 85 - 300 V AC;
- output voltage range: -42 ~ -58 V DC;
- LCD display.
Specification:
ETP4890-A2 | |
General properties |
|
---|---|
Dimensions | 442 x 255 x 86,1 mm (2U) |
Weight | Max. 10 kg |
Installation method | Rack cabinet 19" |
Ingress Protection Code | IP20 |
Input AC | |
Voltage range |
220 / 380 V AC (3 phases) 220 V AC (2 phases) 110 V AC (dual-live wire) |
Frequency range |
45 ~ 66 Hz (recommended: 50 / 60 Hz) |
SPD |
5 kA / 10 kA 8/20μs |
Output DC | |
Voltage range |
-42 ~ -58 V DC (nominal -53,5 V DC) |
Max. output power | 4,8 kW |
Battery switch | 1x 90 A |
Load switches |
1x 10A 1x 30A 2x 40A |
Environmental properties | |
Permissible working temperature | From -40 to 65°C |
Permissible storage temperature | From -40 to 70°C |
Permissible air humidity | 5%-95% non-condensing |
Rectifier R4830N | |
General properties | |
Dimensions | 40,8 x 95,5 x 208 mm |
Weight | Max. 1,5 kg |
Cooling | Active |
MTBF | > 500000 hours |
Volume | ≤ 45dB (25°C, max load) |
Input properties | |
Voltage range | 85 - 300V AC |
Frequency range |
45 - 66 Hz (reccomended 50 / 60 Hz) |
Max current input | < 13A |
Power factor | ≥0.99 (at full load) |
THD |
≤5% |
Output properties | |
Voltage |
-42 ~ -58V DC (nominal -53,5V DC) |
Output power |
1600W (176 - 300V AC) |
Environmental properties | |
Permissible working temperature | From -40 to 75°C |
Permissible storage temperature | From -40 to 75°C |
Permissible air humidity | 5%-95% non-condensing |
Protection
|
|
Input overvoltage protection | Above 300V AC |
Input undervoltage protection | Below 80V AC |
Output overvoltage protection |
56 - 60V DC (can be set manually) |
Output short circuit protection | Prolonged short circuit is allowed |
Overheat protection | Yes |
Certificates/ EMC | |
Certificates |
TUV, CE, UL CB UL60950-1 IEC60950-1 EN60950-1 CAN/CSA C22.2 nr 60950-1 |
EMC |
EN55022 klasa B EN55024 EN61000-3-2 EN61000-3-3 ETSI EN300 386 ETSI EN301489 ITU-T K.20 |
Lightning protection | 5 KA |
SMU01C | |
Signal input | 2 digital input |
Alarm output | 4 dry contact |
Display | LCD |
Communication port and parameter | RS485/RS232: 9600 bits/s or 19,200 bits/s |